Step 3 View active alarms and check that the EPO alarm is cleared. If the system bypass
input is normal, the UPS transfers to bypass mode.
Step 4 Start the inverter.
----End

7.12 Exporting Data

Prerequisites
You have logged in to the WebUI.
Context
The following data can be exported:
Procedure
Step 1 Choose Query > Export Data > Export Historical Data , set Encryption Password
for Export, and select Historical Alarm from the Data Type drop-down list.
Figure 7-22 Exporting historical data
Step 2 Click Export Historical Data and save the displayed webpage.
----End
Issue 03 (2021-08-03)
Choose Monitoring > UPS System > Running Control > System Commands
and Tests and click Clear Faults. The EPO alarm is cleared.
On the LCD
Choose System Info > Alarms > Active Alarms to check that the EPO alarm
has been cleared.
On the WebUI
Choose Home > Active Alarm to check that the EPO alarm has been cleared.
Historical alarms
Active alarms
Performance data
Operation logs
E-label
Fault information
NO TE
This procedure describes how to export historical alarms.
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
173