UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
EMC Test Item
Electrical fast transient
Surge
Impact current (lightning protection)
Voltage dips and short interruptions (220 V AC)
Power frequency magnetic field
Table 11-5 Mains input electrical specifications
Item
400 kVA/500 kVA
Power
Three-phase four-wire + PE
system
Rated
380 V AC/400 V
Voltage
AC/415 V AC (line
voltage)
Issue 03 (2021-08-03)
600 kVA
200 V AC/208 V AC/210
V AC/380 V AC/400 V
AC/415 V AC (line
voltage)
When the voltage is
200 V AC/208 V AC/210
V AC, the power of the
entire system is derated
to 50%.
Copyright © Huawei Technologies Co., Ltd.
Standard
EN/IEC 62040-2
IEC 61000-4-4
EN/IEC 62040-2
IEC 61000-4-5
If a surge protection box is configured: 5 kA
(common mode), criterion B
IEC 61000-4-11
IEC 61000-4-8
800 kVA
380 V AC/400 V AC/415 V AC/480
V AC (line voltage)
11 Technical Specifications