UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
center, and transaction center, the Tier 4 or 3 power architecture specified in
TIA-942 must be used. That is, two power supplies must be used to supply power
to loads.
Ensure that the equipment is used in an environment that meets the product
design specifications (including power grid, temperature, and humidity).
Otherwise, the equipment may become faulty, and the resulting equipment
malfunction and component damage are not covered under the warranty.
The UPS operating environment must meet the requirements for the climate
indicator, mechanically active substance indicator, and chemically active substance
indicator in ETSI EN 300 019-1 class 3.6.
● This is a category C3 UPS product for commercial and industrial application in
● After unpacking the UPS, you are advised to power on the UPS as soon as
● After unpacking batteries, you are advised to connect the battery supply as
● Install the UPS in an area far away from liquids. Do not install it under areas
● If any liquid is detected inside the equipment, immediately disconnect the
● Do not expose the equipment to flammable or explosive gas or smoke. Do not
● During installation and maintenance, ensure that sundries do not enter the
If the valid mains voltage exceeds 320 V AC, the UPS may be damaged.
A UPS can be used to serve resistive-capacitive loads, resistive loads, and micro-
inductive loads. It is recommended that a UPS not be used for pure capacitive
loads, pure inductive loads, and half-wave rectification loads. A UPS does not
apply to regeneration loads.
Issue 03 (2021-08-03)
NO TICE
the second environment − installation restrictions or additional measures may
be needed to prevent disturbances.
possible. If you temporarily do not use the UPS, take appropriate measures to
prevent moisture, dust, and foreign matter from entering the UPS.
soon as possible. If you temporarily do not use the batteries, store them in a
dry and clean environment. If batteries are stored for more than 90 days,
charge them in time. Otherwise, the battery lifespan may be affected.
prone to water leakage, such as air conditioner vents, ventilation vents, or
feeder windows of the equipment room. Ensure that no liquid enters the UPS
to prevent short circuits. Ensure that there is no condensation inside the
equipment or equipment room.
power supply and contact the administrator.
D ANGER
perform any operation on the equipment in such environments.
UPS. Otherwise, equipment damage, load power derating, power failure, and
personal injury may occur.