Setting Communications Parameters (Snmp Protocol) - Huawei NetCol5000-C Series User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Parameter
address
NMS port
number
----End

4.3.4.3 Setting Communications Parameters (SNMP Protocol)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
displayed.
Figure 4-8 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
Issue 07 (2020-03-16)
Setting
N/A
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a smart
cooling product to an EMS (element management system).
One smart cooling product supports concurrent access of up to 6 EMSs through SNMP.
If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read Community and
Write Community by performing
Copyright © Huawei Technologies Co., Ltd.
Setting Method
the display panel, EMS client, and EMS server must be
unique. This parameter is configurable when Link mode
is set to Client.
It is recommended that you retain the default value. If you
need to change the value, enter a value as required. This
parameter is configurable when Link mode is set to
Client.
Step
3.
4 Commissioning
Figure 4-8
is
83