NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Figure 3-7 Pipe supports (unit: mm)

3.1.3.6 Cables

The cable flame spread rating must be at least VB.
The following lists the cables and devices to be connected. When connecting cables, fit them
with protective hoses.
Table 3-4 Cables and switches required
Name
Power cable
Teamwork
networking and
monitoring cable
Fuse
OT terminal
Issue 07 (2020-03-16)
The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including the thermal
insulation foam).
Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away from each
bending point in turning sections.
Specifications
Electronic|Electric Cable,
600 V/1000 V, ZA-RVV,
3 x 6 mm
Cores: Brown, Blue,
Yellow/Green), 46 A,
Outdoor Cable, CE
Signal cable, Shielded
straight-through cable, 10
m, MP8-II, CC4P0.5GY
(S), MP8-II, FTP
Slow Blow Fuse, 250 V,
4 A, IEC Specification,
0.03 ohm, 38.7 A x A x
Sec, UL/CSA Approved
Naked Crimping
Terminal, OT, 6 mm
Copyright © Huawei Technologies Co., Ltd.
Quantity
2 PCS
2
, Black (3
1 PCS
2 PCS
6 PCS
2
,
3 Installation
Remarks
Optional; same cable
parameters for the active
and standby routes
Optional
Standard configuration;
delivered with the
product
Standard configuration;
delivered with the
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c065Netcol5000-c080

Table of Contents