User Manual
7.2.3 How Can I View Active Alarms and Historical Alarms?
Procedure
Step 1 Log in to the smart cooling product WebUI as an administrator.
Step 2 Choose Home > Active Alarm to view the active alarms of the smart cooling product. Click
Details in the Alarm Description area to view alarm details of devices.
Step 3 To view historical alarms, choose Query > Historical Alarm, set Equipment, Start time,
End time, and Sorting Mode, and click Query.
----End
7.2.4 How Can I Export or Import a Configuration File?
Context
You can export parameter configurations for smart cooling product 1 to a PC. If smart cooling
product 2 needs the same parameter configurations, import the configuration file to smart
cooling product 2.
Procedure
Step 1 Log in to the smart cooling product 1 WebUI as an administrator.
Step 2 Choose Maintenance > Configuration File.
Step 3 Export a configuration file.
1.
2.
Step 4 Import a configuration file.
The smart cooling product 2 will restart after you import the configuration file.
1.
2.
3.
4.
5.
----End
Issue 07 (2020-03-16)
(Optional) Specify Configuration File Encryption Password.
Record the password for importing a configuration file.
Click Back Up Current Settings.
Log in to the smart cooling product 2 WebUI as an administrator.
Choose Maintenance > Configuration File.
Specify Configuration File Decryption Password.
Click Browse on the right of Import a new configuration file.
Select the configuration file to be imported, and click Upload.