Huawei NetCol5000-C Series User Manual page 68

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Figure 3-38 Cables routed outside the cabinet
Step 2
Table 3-5
Figure 3-39 DIP switches
Table 3-5 DIP switch setting on a T/H sensor
Position
Name
Return air
Return air 2
temp/humid
Cold aisle
Cold aisle 1
Issue 07 (2020-03-16)
The T/H sensors inside the cabinet are secured at the return air side and their IN ports are connected
to the main control board. When connecting the T/H sensors outside the cabinet, connect the OUT
port of one T/H sensor inside the cabinet to the IN port of the next T/H sensor outside the cabinet.
Connect all T/H sensors in series in this way.
The T/H sensors should be 1.5 m above the ground (33 U).
Each smart cooling product supports a maximum of ten T/H sensors.
shows how to set the DIP switches for T/H sensors.
Address DIP Switch ID
1
11
Copyright © Huawei Technologies Co., Ltd.
1
2
3
ON
OFF
OFF
ON
ON
OFF
3 Installation
4
5
6
OFF
OFF
OFF
ON
OFF
OFF
60