Signal Ports; Connecting The Teamwork Network Cable; Connecting The Fe Teamwork Network Cable - Huawei NetCol5000-C Series User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual

3.12.4.2 Signal Ports

Figure 3-31 Signal ports
(1) Common alarm 2 (ALM_2 COM)
(3) Common alarm 1 (ALM_1 COM)
(5) External water sensor (Water -)
(7) Remote on/off (Remote COM)
(9) Smoke sensor (Smoke AI)

3.12.4.3 Connecting the Teamwork Network Cable

3.12.4.3.1 Connecting the FE Teamwork Network Cable

Procedure
Step 1 (Optional) Make FE teamwork network cables by referring to
Issue 07 (2020-03-16)
Smart cooling products in a teamwork group must be of the same model.
The default networking mode is CAN networking.
The smart cooling product supports two teamwork networking modes: FE teamwork
networking and CAN teamwork networking (hand-in-hand).
Copyright © Huawei Technologies Co., Ltd.
(2) Common alarm 2 (ALM_2 NO)
(4) Common alarm 1 (ALM_1 NO)
(6) External water sensor (Water +)
(8) Remote on/off (Remote +)
(10) Smoke sensor (Smoke 12VDC)
Figure 3-32
3 Installation
if required onsite.
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c065Netcol5000-c080

Table of Contents