Huawei NetCol5000-C Series User Manual page 149

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Alarm
ID
A092-01
Issue 07 (2020-03-16)
Alarm
Alarm
Name
Severit
y
g
low
temperatur
e alarm
Hot aisle
Warnin
low
g
temperatur
e alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Impact
Possible Cause
alarm is
temperature and
triggere
humidity sensors
d.
are located in
inappropriate
positions.
2. The thermal load
power is low.
3. The ambient
temperature is
below the lower
threshold.
4. The low
temperature
alarm threshold
is inappropriate.
5. The value
detected by the
temperature
sensor or
temperature and
humidity sensor
is different from
the actual value.
6. The air filters are
blocked.
7. The chilled water
valve is stuck or
faulty.
1. The temperature
An
sensors or
alarm is
temperature and
triggere
humidity sensors
d.
are located in
inappropriate
positions.
2. The thermal load
power is low.
3. The ambient
temperature is
below the lower
threshold.
4. The low
temperature
alarm threshold
Solution
temperature
sensors or
temperature and
humidity
sensors.
Step2.Contact
Huawei technical
support.
2. Measure the
ambient
temperature.
Check whether
other causes
exist if the alarm
persists in a long
time after
startup.
3. Adjust the low
temperature
alarm threshold.
4. Calibrate or
replace the
temperature
sensor or
temperature and
humidity sensor.
5. Maintain or
replace the air
filters.
6. Maintain or
replace the
chilled water
valve.
1. Adjust the
positions of the
temperature
sensors or
temperature and
humidity
sensors.
Step2.Contact
Huawei technical
support.
2. Measure the
ambient
temperature.
Check whether
other causes
exist if the alarm
persists in a long
141

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c065Netcol5000-c080

Table of Contents