Huawei NetCol5000-C Series User Manual page 158

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Alarm
ID
Issue 07 (2020-03-16)
Alarm
Alarm
Name
Severit
y
Cold aisle
Major
1
temp/humi
d sensor
fault
Cold aisle
Major
2
temp/humi
d sensor
fault
Cold aisle
Major
3
temp/humi
d sensor
fault
Cold aisle
Major
4
temp/humi
d sensor
fault
Cold aisle
Major
5
temp/humi
d sensor
fault
Hot aisle 1
Major
temp/humi
d sensor
fault
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Impact
Possible Cause
sensor is faulty.
1. The cables to the
An
temperature and
alarm is
humidity sensor
triggere
are loose or
d.
damaged.
2. The temperature
and humidity
sensor is faulty.
1. The cables to the
An
temperature and
alarm is
humidity sensor
triggere
are loose or
d.
damaged.
2. The temperature
and humidity
sensor is faulty.
1. The cables to the
An
temperature and
alarm is
humidity sensor
triggere
are loose or
d.
damaged.
2. The temperature
and humidity
sensor is faulty.
1. The cables to the
An
temperature and
alarm is
humidity sensor
triggere
are loose or
d.
damaged.
2. The temperature
and humidity
sensor is faulty.
1. The cables to the
An
temperature and
alarm is
humidity sensor
triggere
are loose or
d.
damaged.
2. The temperature
and humidity
sensor is faulty.
1. The cables to the
An
temperature and
alarm is
humidity sensor
triggere
are loose or
d.
damaged.
2. The temperature
and humidity
Solution
humidity sensor.
1. Check the cables
to the
temperature and
humidity sensor.
2. Maintain or
replace the
temperature and
humidity sensor.
1. Check the cables
to the
temperature and
humidity sensor.
2. Maintain or
replace the
temperature and
humidity sensor.
1. Check the cables
to the
temperature and
humidity sensor.
2. Maintain or
replace the
temperature and
humidity sensor.
1. Check the cables
to the
temperature and
humidity sensor.
2. Maintain or
replace the
temperature and
humidity sensor.
1. Check the cables
to the
temperature and
humidity sensor.
2. Maintain or
replace the
temperature and
humidity sensor.
1. Check the cables
to the
temperature and
humidity sensor.
2. Maintain or
replace the
temperature and
150

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c065Netcol5000-c080

Table of Contents