NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Alarm Parameters
Parameters of Teamwork Settings
Number of smart cooling products in this group ≥ Number of running smart cooling products
in this group
Parameters of Cooling cap. mgt.
Upper limit of water supply temperature > Lower limit of water supply temperature
Parameters of Indoor fan
Parameters of System Control
Issue 07 (2020-03-16)
Supply air high temperature alarm threshold + 5°C ≤ Return air high temperature alarm
threshold
Supply air high temperature alarm threshold + 5°C ≤ Hot aisle high temperature alarm
threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Hot aisle high temperature alarm
threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Return air high temperature alarm
threshold
Supply air low temperature alarm threshold + 5°C ≤ Return air low temperature alarm
threshold
Supply air low temperature alarm threshold + 5°C ≤ Hot aisle low temperature alarm
threshold
Cold aisle low temperature alarm threshold + 5°C ≤ Hot aisle low temperature alarm
threshold
Cold aisle low temperature alarm threshold + 5°C ≤ Return air low temperature alarm
threshold
Min indoor fan speed ≤ Min indoor fan speed in silent mode ≤ Medium indoor fan speed
in silent mode ≤ Max indoor fan speed in silent mode ≤ Max indoor fan speed
Min return/supply air temp difference in silent mode ≤ Medium return/supply air temp
difference in silent mode ≤ Max return/supply air temp difference in silent mode
Min indoor fan speed ≤ Min speed for humidifying ≤ Max indoor fan speed
Min indoor fan speed ≤ Lower limit of max speed for dehumidifying ≤ Upper limit of
max speed for dehumidifying ≤ Max indoor fan speed
Indoor fan min return/supply air temperature difference ≤ Indoor fan max return/supply
air temperature difference
Only when Air-side difference pressure sensor type is set to 0~50Pa or Differential
pressure sharing is enabled, Indoor fan control type can be set to Pressure diff ctrl.
When Indoor fan control type is set to Pressure diff ctrl, Air-side difference pressure
sensor type can not be set to No or 0~500Pa.
When Indoor fan control type is not set to Pressure diff ctrl, Air-side difference
pressure sensor type can not be set to 0~500Pa.
Cooling start temperature demand > Cooling stop temperature demand