Securing The Netcol5000-C; Connecting Water Pipes; Connect Automatic Drainpipe - Huawei NetCol5000-C Series User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Figure 3-19 Combining cabinets (rear door)
1.
2.
Step 3 Secure the connecting kits at the connection positions on the rear door using screws in the
same way.
----End

3.7 Securing the NetCol5000-C

Secure the smart cooling product to the base. If there are no bases onsite, prepare one by
referring to

3.8 Connecting Water Pipes

3.8.1 Connect Automatic Drainpipe

Context
Issue 07 (2020-03-16)
Remove the connecting kits from the cabinets.
Secure the connecting kits at the connection positions on the front door using screws.
Ensure that the vertical distance between each device top and the floor is 2000 mm (± 2 mm) or 2500
mm (± 2 mm) and that all device tops are on the same plane.
C Base
Dimensions.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
42

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c065Netcol5000-c080

Table of Contents