NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Alarm
ID
A051-01
Issue 07 (2020-03-16)
Alarm
Alarm
Name
Severit
y
temperatur
e alarm
Hot aisle
Critical
high
temperatur
e alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Impact
Possible Cause
triggere
temperature and
d.
humidity sensors
are located in
inappropriate
positions.
2. The thermal load
power is high or
the cooling
capacity is
insufficient.
3. The ambient
temperature
exceeds the
upper threshold.
4. The high
temperature
alarm threshold
is inappropriate.
5. The value
detected by the
temperature
sensor or
temperature and
humidity sensor
is different from
the actual value.
6. The chilled water
flow is
insufficient, or
the supply water
temperature is
high.
7. The chilled water
valve is stuck or
faulty.
1. The temperature
An
sensors or
alarm is
temperature and
triggere
humidity sensors
d.
are located in
inappropriate
positions.
2. The thermal load
power is high or
the cooling
capacity is
insufficient.
3. The ambient
Solution
temperature
sensors or
temperature and
humidity
sensors.
2. Add smart
cooling products
or contact
Huawei technical
support.
3. Measure the
ambient
temperature.
Check whether
other causes
exist if the alarm
persists in a long
time after
startup.
4. Adjust the high
temperature
alarm threshold.
5. Calibrate or
replace the
temperature
sensor or
temperature and
humidity sensor.
6. Check the
pressure and
temperature of
chilled water.
7. Maintain or
replace the
chilled water
valve.
1. Adjust the
positions of the
temperature
sensors or
temperature and
humidity
sensors.
2. Add smart
cooling products
or contact
Huawei technical
support.
3. Measure the
134