NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Parameter
Cascade
function
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
teamwork control succeeds, the teamwork topology of the smart cooling product in the group
is displayed, as shown in
Figure 4-7 Teamwork topology
Table 4-7 Notes for the screen
No.
1
2
3
Issue 07 (2020-03-16)
Description
After the requirement
control is enabled, you
can configure Cascade
function. The cascade
function starts standby
smart cooling products if
the active one cannot
meet the refrigerating
requirements.
2.
Figure
Parameters
Note
On/Off
On indicates that the smart cooling product is started and Off
indicates that the smart cooling product is shut down.
01, 02, 03
Indicates the smart cooling product address. 01 is the master one
and the rest are all slave ones.
NOTE
If the master one offline, the teamwork networking failed.
Active/Stand
Active: properly responds to the requirement control.
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
If the heat load to the
device increases, the
cascade function is
recommended.
4-7.
Table 4-7
describes the note for the screen.
4 Commissioning
Default
Value
Disable
Step 1
and
. If the
79