NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Menu
Date & Time
Settings
Teamwork
Settings (visible
for V200R002
version)
Issue 07 (2020-03-16)
Parameter
Description
Date format
Specifies the date
display format for
the ACC.
Date settings
Specifies the date
displayed on the
ACC.
Time
Specifies the time
displayed on the
ACC.
Time zone
Specifies the time
zone displayed on
the ACC.
Teamwork
Set the assigned
group No.
teamwork control
number.
Air
Set the assigned unit
address.
conditioner
address
Teamwork
Disable or enable
function
the teamwork
function. If the
teamwork function
is disabled, this
device is operating
according to its own
control. If the
teamwork function
is enabled, this
device works in
harmony with others
that in the same
group.
Networking
Networking mode
mode
for the teamwork.
The networking
mode set on the
screen must be
consistent with the
actual networking
mode. Otherwise,
the teamwork
control function will
be unavailable.
Number of
Number of the smart
smart cooling
cooling products in
products in
this group (1 to 32
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
Set the parameter according to
reading habits.
Set the parameter according to
the actual situation.
Set the parameter according to
the actual situation.
Set the parameter according to
the actual situation.
The number of the teamwork
controlled group, which is the
same for all the devices in the
group.
Air conditioner addresses should
be different from each other.
Set this parameter based on the
onsite device heat distribution.
Networked over CAN or
MAC_CAN. CAN network
indicates teamwork control over
a CAN bus, MAC_CAN
network teamwork control over
an FE port.
Total number of the smart
cooling products in this group.
66