Replacing The Wet Film Humidifier - Huawei NetCol5000-C Series User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual

6.4.5 Replacing the Wet Film Humidifier

Prerequisites
On the home page, choose Maint > Performance Maint to query the runtime of the wet film
humidifier. If the value is 8760 h, the system automatically generates a message. You are
advised to change the wet film humidifier now.
Context
Tool: Phillips screwdriver
Procedure
Step 1 Choose Settings > System Settings > System Control > Humid > Disable.
Step 2 Open the rear door, remove the air filter, and switch off general circuit breakers (AC1 and
AC2).
Step 3 Use a Phillips screwdriver to remove the screws and sheet metal fasteners.
Figure 6-4 Replacing a wet film humidifier
Step 4 Hold the release sleeve and remove the water inlet pipe.
Step 5 Draw out the old wet film humidifier.
Step 6 Install the new wet film humidifier by performing
After the replacement is complete, properly install the water inlet pipes to the wet film
humidifier. Ensure that the water inlet pipes are secured without leakage risks.
Step 7 Open the rear door, installation the air filter, and Turn on the AC1 and AC2 switches.
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Step 4
to
Step
1.
160

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c065Netcol5000-c080

Table of Contents