NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Table 2-3 Pipe Ports
Item
Water outlet pipe
Water inlet pipe
(Optional) Humidifier water inlet pipe
Automatic drainpipe
Installation Requirements
Table 2-4 Installation Requirements
Item
Room door
Floor
Pipe routing
Cabling mode
Drainage requirements
Water supply requirements of wet film
Power distribution
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
Description
G 1–1/2 in. port with inner threads
G 1–1/2 in. port with inner threads
G 1/2 in. port with inner threads
BSPP 1/2 in. port with inner threads
Description
2000 mm high: width ≥ 1.2 m, height ≥
2.3 m. The cabinet may topple over in a
short time.
2500 mm high: width ≥ 1.2 m, height ≥
2.8 m. The cabinet may topple over in a
short time.
Floor bearing capacity ≥ 530 kg/m
Floor height ≥ 300 mm
Bottom pipe routing
Top cabling
Automatic drainage
The inlet water pressure should be in the
range of 0.1–0.7 MPa (A reducing valve
must be installed if the inlet water pressure
exceeds 0.7 MPa.), and the temperature
should be in the range of 1° C–40° C.
The wet film humidifier should use tap
water (no water treatment facility needed
for the inlet water) that meets the following
requirements:
Non-freezing and nephelometric
turbidity units (NTU): < 3
No visible substances
6.5 ≤ pH value ≤ 8.5
Total hardness (in CaCO
Leakage circuit breakers are not used for the
main power route. If leakage circuit
breakers are required by the customer or by
local regulations, use the residual current
2 Product Description
2
): ≤ 450 mg/L
3
21