NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
7.1.11 Clearing the Runtime
Context
Performance value clearance can be performed only after component maintenance. Otherwise
the component may run overtime and degrade performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Figure 7-14 Performance Maint screen
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End
7.1.12 Calibrating a Sensor
Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates from the
actual value. For example, if the return air temperature measured by other temperature
detection devices at the return air detection point is 20° C while the value measured by the
sensor is 22° C, the sensor has an error of 2° C, and the calibration value should be set to –2° C.
Procedure
Step 1 On the home screen, choose Maint > Sensor Calibration.
Step 2 Fill the calibration value based on the measured error.
----End