NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Menu
Issue 07 (2020-03-16)
Parameter
Description
Temperature
This parameter
control mode
controls the
temperature inside
the room or aisles
based on the
Average value,
Max value, or Min
value of the
temperatures
collected by each
sensor.
Temperature
After the
setpoint
Temperature and
humidity control
type and the
temperature value
under this type are
set, the device
conducts cooling or
heating based on the
settings.
Humidity
After the
setpoint
Temperature and
humidity control
type and the
humidity value
under this type are
set, the device
conducts
humidifying or
dehumidifying based
on the settings.
Cold aisle
The sensors in cold
sensor 1
aisles can be set to
Enable or Disable.
Cold aisle
sensor 2
Cold aisle
sensor 3
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Configuration Principle
choose Cold aisle if the cold
aisle T/H sensors are
configured.
Hot aisle is not
recommended.
Average value: Select
Average value if the
temperature is to be
controlled based on the
averaged data value collected
by the collector.
Max value: Select Max
value if the temperature is to
be controlled based on the
maximum data value
collected by the collector.
Min value: Select Min value
if the temperature is to be
controlled based on the
minimum data value
collected by the collector.
Set this parameter as required.
Return air temperature:
26–35° C recommended
Supply air temperature:
18–24° C recommended
Cold aisle temperature:
18–24° C recommended
Hot aisle temperature:
26–35° C recommended
Set this parameter as required.
40%–60% RH recommended
The cold aisle sensors outside
the cabinet need to be enabled
when they are installed.