Procedure
Step 1 Tap Shutdown on the LCD home screen.
Exercise caution because the device is still energized after it is shut down on the LCD.
Step 2 Open the front door.
Step 3 Use a Phillips screwdriver to loosen the R-shaped pipe clip that secures the supply air
temperature sensor on the front door post, and remove the supply air temperature sensor probe,
as shown in
Figure 6-8 Position of the supply air temperature sensor
Step 4 Remove the waterproof connector from the temperature sensor cable and remove the supply
air temperature sensor probe.
Step 5 Secure the new supply air temperature sensor cable to the original position using cable ties,
and fix the sensor probe using the R-shaped pipe clip.
Step 6 Reconnect the waterproof connector to the sensor cable.
Step 7 Close and lock the front door.
----End