Parameter
period
Rotation time
Forced rotation
Requirement
control
Issue 07 (2020-03-16)
Description
24 hours in a day (0–23).
Forced rotation
specifies whether to
enable a forcible rotation
on the group before the
specified rotation time.
After a forced rotation,
the accumulated time is
recalculated.
Enable or disable the
requirement control for
the master device.
When the requirement
control is Disable, the
master device does
not synchronize data
to the slave device,
and all the smart
cooling products
operate based on their
own requirements, not
referring to the mode
delivered by the
master device.
When the requirement
control is
Anti-competitive
running, the master
device synchronizes
data (the temperature
and humidity control
type and set points of
the master device and
other parameters) to
the slave device, and
all the smart cooling
products in the group
refer to the mode
delivered by the
master device.
When the requirement
control is Indoor fan
unified control, all
smart cooling product
fans in the group
rotate at the same
speed.
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
0 by default
This item is set to No by
default. If forced rotation
is required, the function is
set to Yes.
Anti-competitive running
is recommended for the
following scenario: In one
teamwork, the temperature
and humidity control type
and temperature and
humidity set point of units
are the same, and device
heat loads are distributed
evenly.
4 Commissioning
Default
Value
0
No
Disable