Figure 3-17 Leveling a cabinet
Wrench an anchor bolt clockwise to elevate a cabinet, wrench an anchor bolt anticlockwise
to lower a cabinet. The leveling feet can be adjusted within a range of 0–8 mm.
To prevent damaged caused by cabinet tilt, adjust all the leveling feet at the four corners
instead of one foot.
Use a measuring tape to check that the vertical distance between the top of the cabinet and
the floor is 2000 mm± 2 mm or 2500 mm± 2 mm.
Do not remove the leveling feet. Otherwise, you need to rework them for use.