Huawei NetCol5000-C Series User Manual page 80

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Figure 4-4 Setting temperature and humidity values
Step 2 Set Cold aisle sensor 1 to Enable.
Step 3 Set the temperature and humidity values by referring to
You are not recommended to modify the parameters not listed in
Table 4-4 Parameter description
Parameter
Temperature and
humidity control
type
Temperature
control mode
Issue 07 (2020-03-16)
Description
Cold aisle, Hot aisle, Return
air, or Supply air can be set as
required. The temperature and
humidity set points correspond
to the selected control type can
be set.
This parameter controls the
temperature inside the room or
aisles based on the Average
value, Max value, or Min value
of the temperatures collected by
each sensor.
Copyright © Huawei Technologies Co., Ltd.
4 Commissioning
Table
4-4.
Table
4-4.
Configuration Principle
When the application scenario is
cold or hot aisle containment,
you are advised to choose Cold
aisle if the cold aisle T/H
sensors are configured, and
choose Supply air if the cold
aisle T/H sensors are not
configured.
When the application scenario is
non-aisle containment, you are
advised to choose Return air,
and choose Cold aisle if the
cold aisle T/H sensors are
configured.
Hot aisle is not recommended.
Average value: Select Average
value if the temperature is to be
controlled based on the averaged
data value collected by the
collector.
Max value: Select Max value if
the temperature is to be
controlled based on the
maximum data value collected
by the collector.
Min value: Select Min value if
72

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c065Netcol5000-c080

Table of Contents