Parameter list
PNU
Description
n748
SLB Diagnosis
(2748)
Visualization parameter which displays diagnostic information for an
installed SIMOLINK board (SLB)
(Z121)
i001: Number of error-free synchronizing telegrams
i002: Number of CRC errors
i003: Number of timeout errors
i004: Last accessible bus address
i005: Address of node sending the special telegram "Timeout"
i006: Implemented bus cycle time
i007: Number of new configurations
i008: Reserved
...
i016: Reserved
U749
SLB Read address
(2749)
Definition of node addresses and channels from which the SLB must read
data (a total of 8 channels can be read according to the index entries). The
*
digits before the decimal point in the input value define the node address
and those after the point the channel number (see also Section 7 "Starting
up SIMOLINK boards" and Section 8, Sheet Z122).
(Z122)
Example:
2.0 = address 2 channel 0
n750
SLB Receive data
(2750)
Visualization parameter for data received via the SIMOLINK board (see also
Section 7 "Starting up SIMOLINK boards" and Section 8 , Sheet Z122)
(Z122)
i001: Word 1 in PZD section of telegram
...
i016: Word 16 in PZD section of telegram
U751
SLB Transmit data selection
(2751)
Selection of connectors whose contents must be transferred as transmit
data by the SLB (see also Section 7 "Starting up SIMOLINK boards" and
*
Section 8 , Sheet Z122).
0 = connector K0000
(Z122)
1 = connector K0001
etc.
In addition to the transmit data itself, its place in the transmit telegram is
also defined.
i001: Channel0, low word
i002: Channel0, high word
...
i015: Channel7, low word
i016: Channel7, high word
n752
SLB Display of transmit data
(2752)
Process data transmitted by SLB via SIMOLINK in hexadecimal notation
(see also Section 7 "Starting up SIMOLINK boards" and Section 8 , Sheet
(Z122)
Z122)
U753
SLB Fault delay
(2753)
Delay in activation of fault message F015 (see also U741)
*
0 = fault message is activated immediately the telegram failure monitor
(Z121)
responds
11-164
Value range
[Unit]
Steps
[SW 1.5 and later]
0.0 to 200.7
[SW 1.5 and later]
0.1
[SW 1.5 and later]
All connector
[SW 1.5 and later]
numbers
[SW 1.5 and later]
[SW 1.5 and later]
0.0 to 100.0
[s]
0.1
SIMOREG DC Master
05.05
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 16
P052 = 3
Type: O2
Ind: 8
P052 = 3
FS=0.0
P051 =40
Type: O2
Offline
Ind: 16
P052 = 3
Type: L2
Ind: 16
P052 = 3
FS=0
P051 =40
Type: L2
Offline
Ind: 16
P052 = 3
Type: L2
Ind: None
P052 = 3
FS=0.0
P051 =40
Type: O2
Offline
SIEMENS AG
6RX1700-0AD76
Operating Instructions