Faults / Alarms
Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
5
Parameters P918, U711 to U721 are not correctly set or
not accepted after a change by means of U710 = 0
setting. (The meanings of these parameters are defined
in the manual for the relevant CB board, see also function
diagrams, Section 8, Sheets Z110 and Z111)
6
The initialization run for a CB/TB board has not been
completed within 40 s
F081
CB/TB heartbeat error
CB/TB has not incremented the monitoring counter for a period
of 800 ms
Possible causes of fault
♦ CB/TB board is defective
CB/TB board is not correctly installed
F082
CB/TB message timeout or error in data exchange
Possible causes of fault
♦ CB/TB PZD message timeout (with fault value 10)
♦ Excessive EMC-related interference
(e.g. due to unprotected contactors, unscreened cables, loose screen connections)
♦ CB/TB board is defective
♦ CB/TB board is not correctly inserted
Fault value (r949 index 001):
1
Fault in alarm channel from CB to basic unit
2
Fault in alarm channel from TB to basic unit
3
Fault in fault channel from TB to basic unit
5
Fault in parameter job channel from CB to basic unit
6
Fault in parameter response channel from basic unit to
CB
7
Fault in parameter job channel from TB to basic unit
8
Fault in parameter response channel from basic unit to
TB
10
CB/TB process data failure (message timeout period set
in U722)
11
Fault in parameter job channel from PMU to TB
12
Fault in parameter response channel from TB to PMU
15
Fault in setpoint channel from CB/TB to basic unit
16
Fault in actual value channel from basic unit to CB/TB
10.1.2.14 Fault messages from supplementary boards
This group of fault messages is activated by supplementary boards
F101
Please refer to the operating manual of the relevant supplementary board for explanation of the fault messages and fault values
to
F147
10-24
Description
Further information (r047.002 to r047.016)
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
r047 Index 002 to 016:
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
i015 Code number of board:
st
1
1
TB or 1
nd
2
2
CB
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
i015 Code number of board:
st
1
TB or 1
CB
nd
2
2
CB
SIMOREG DC Master
st
CB
SIEMENS AG
6RX1700-0AD76
Operating Instructions
05.05

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents