Parameter list
PNU
Description
11.3
Access authorization levels
P051
Key parameters
*
0
No access authorization
6
Do not set (for use by DriveMonitor)
7
Do not set (for use by DriveMonitor)
9
Do not set (for use by DriveMonitor)
21
Restore factory settings
All parameters are reset to their defaults (factory settings).
Parameter P051 is then automatically reset to factory setting
"40".
22
Execute internal offset compensation (see Section 7.4)
25
Optimization run for precontrol and current controller (armature
and field) (see Section 7.5)
26
Optimization run for speed controller (see Section 7.5)
27
Optimization run for field weakening (see Section 7.5)
28
Optimization run for compensation of friction and moment of
inertia (see Section 7.5)
29
Optimization run for the speed controller with an oscillating
mechanical system (see Section 7.5)
40
Access authorization to parameter values for authorized service
personnel
P052
Selection of display parameters
*
0
0
Display only parameters that are not set to original factory
settings
1
Display only parameters for simple applications
3
Display all parameters used
P053
Control word for the permanent memory
*
Disabling or enabling write accesses to the permanent memory
i001:
Disabling or enabling write accesses to the parameter memory
0
Only save parameter P053 in the permanent memory;
parameter changes are active immediately but the changed
values are only stored temporarily and are lost when the
electronics supply voltage is switched off
1
Save all parameter values in the permanent memory
i002:
Disabling or enabling write accesses to the memory of the
nonvolatile process data
0
Do not save nonvolatile process data in the permanent
memory
1
Save all nonvolatile process data in the permanent memory
If the nonvolatile process data are not stored (P053.002=0),
data are lost when the electronics supply of the SIMOREG DC
Master is switched off, i.e. they have the value 0 after the
electronics supply is switched on again:
K0240: Setpoint of the motor potentiometer
K0309: Motor heating
K0310: Thyristor heating
K9195: Output of the 1st tracking/storage element
K9196: Output of the 2nd tracking/storage element
P054
OP1S – Background lighting
0
ON continuously
1
ON when panel is in use
11-12
Value range
[Unit]
Steps
see column on left
0, 1, 3
0 to 1
[SW 1.7 and later]
1
0, 1
SIMOREG DC Master
05.05
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=40
P051 ≥ 0
Type: O2
Online
Ind: None
P052 = 3
FS=3
P051 ≥ 0
Type: O2
Online
Ind: 2
P052 = 3
FS=1
P051 = 0
Type: O2
on-line
Ind: None
P052 = 3
FS=0
P051 ≥ 0
Type: O2
Online
SIEMENS AG
6RX1700-0AD76
Operating Instructions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents