Siemens 6RA7086-6KS22 Operating Instructions Manual page 169

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
2. Pulse encoder type 1a
3. Pulse encoder type 2
4. Pulse encoder type 3
P141
Number of pulses of pulse encoder (in pulses/rev)
P142
Matching to pulse encoder signal voltage
0 Pulse encoder outputs 5 V signals
1 Pulse encoder outputs 15V signals
Matching of internal operating points to signal voltage of incoming pulse encoder
signals.
NOTICE
Resetting parameter P142 to the alternative setting does not switch over the supply
voltage for the pulse encoder (terminals X173.26 and 27).
Terminal X173.26 always supplies +15V. An external voltage supply must be
provided for pulse encoders requiring a 5V supply.
P143
Setting the maximum speed for pulse encoder operation (in pulses/rev)
The speed set in this parameter corresponds to an actual speed (K0040) of 100%.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Encoder with two pulse tracks mutually displaced by 90° (with/without zero marker).
The zero marker is converted internally to a signal in the same way as on encoder
type 1.
Track 1
X173 28, 29
Track
X173 30, 31
Zero marker
X173 32, 33
internal zero marker
Encoder with one pulse track per direction of rotation (with/without zero marker).
CW rotation
Track 1
X173 28, 29
Track 2
X173 30, 31
Zero marker
X173 32, 33
Encoder with one pulse track and one output for direction of rotation (with/without
zero marker).
CW rotation
Track 1
Pulse output
X173 28, 29
Track 2
Rot. direction
X173 30, 31
Zero marker
Zero marker
X173 32, 33
≤ 360°
225 ± 60°
Hübner OG9DN, POG9DN
Teldix Rotaswitch Serie 25
Honeywell HDM Series
CCW rotation
CCW rotation
Start-Up
7-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents