05.05
PNU
Description
r992
List of modified parameter numbers, continuation
See r990.
r993
List of modified parameter numbers, continuation
See r990.
r994
List of modified parameter numbers, continuation
See r990.
r995
List of modified parameter numbers, continuation
See r990.
r996
List of modified parameter numbers, continuation
See r990.
r997
List of modified parameter numbers, continuation
See r990.
r998
List of modified parameter numbers, continuation
See r990.
r999
List of modified parameter numbers, continuation
Continuation of the list can be found under index 101. Please note:
2990
=
n990
See also r990.
11.52 Password protection, key/lock mechanism
Key/lock mechanism
To prevent unintended parameterization of the devices and to protect the know-how stored in the parameterization, you can restrict
access to the (basic converter) parameters and define your own passwords (=pairs of numbers that you can choose). This done in
parameters:
U005 key and
U006 lock.
If U005 and U006 are parameterized differently, it is only possible to access the following parameters:
All visualization parameters (rxxx, nxxx)
All parameters that can be changed with P051 = 0 (See parameter list)
All "user parameters" (see Parameter U007)
All other parameters neither be read nor altered.
Only when U005 and U006 are parameterized to the same values, are these restrictions removed again.
When using the key-lock-mechanism you should follow this procedure:
1. Program the den lock parameter U006 in both parameter indices with your specific password.
2. Set Parameter P051 to the value 0. This activates the password you have just set (in U006).
After that, P051 can be set to 40 again and the password protection remains active.
Examples:
Lock
U006.1 = 0 (factory setting)
U006.2 = 0
U006.1 = 12345
U006.2 = 54321
U006.1 = 12345
U006.2 = 54321
NOTE:
If you forget or lose your password, you can only regain access to all parameters by restoring the factory setting (P051=21).
U005
Key
(2005)
Parameter for entering the keys for the key/lock mechanism
*
U006
Lock
(2006)
Parameter for entering the password for the key/lock mechanism
*
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Key
U005.1 = 0 (factory setting)
U005.2 = 0
U005.1 = 0
U005.2 = 0
U005.1 = 12345
U005.2 = 54321
Value range
[Unit]
Steps
Result
The key and lock are parameterized identically,
all parameters are accessible
The key and lock are parameterized differently,
only the visualization parameters, the parameters that can be
altered with P051=0, and the "user parameters" are accessible
The key and lock are parameterized identically,
all parameters are accessible
[SW 1.7 and later]
0 to 65535
1
[SW 1.7 and later]
0 to 65535
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 101
P052 = 3
Type: O2
Ind: 101
P052 = 3
Type: O2
Ind: 101
P052 = 3
Type: O2
Ind: 101
P052 = 3
Type: O2
Ind: 101
P052 = 3
Type: O2
Ind: 101
P052 = 3
Type: O2
Ind: 101
P052 = 3
Type: O2
Ind: 101
P052 = 3
Type: O2
Ind: 2
P052 = 3
FS=0
P051 = 0
Type: O2
on-line
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: O2
on-line
11-99