Siemens 6RA7086-6KS22 Operating Instructions Manual page 208

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

Start-Up
DeviceNet Response
This object is used to respond to requests of the above type and 8 bytes in length.
Byte
1
2
3
4
5
6
7
8
Examples
Read parameter P101.004 using GET Single (for details in the shaded data area, see also Section
7, Starting up PROFIBUS boards):
Byte
1
2
3
4
5
6
7
8
9
Request identifier = 0x6065 (request parameter value (array) P101), Index = 0004h = 4d
Response by SIMOREG:
Byte
1
2
3
4
5
6
7
8
Response identifier = 0x4065, value of P101.004 = 0190h = 400d (PWE2 remains unused because
it is not a double word parameter)
7-50
DeviceNet identification
[FRAG] [XID] [SRC/DST MAC ID]
[R/R] [Service]
PKE
PWE1
PWE2
DeviceNet identification
[FRAG] [XID] [SRC/DST MAC ID]
[R/R] [Service]
Class
Instance
Attribute
PKE
IND
DeviceNet identification
[FRAG] [XID] [SRC/DST MAC ID]
[R/R] [Service]
PKE
PWE1
PWE2
0x8E
[Get/Set_Attribute_Single]
0x90
Parameter ID, L byte
Parameter ID, H byte
Parameter value, L word, L byte
Parameter value, L word, H byte
Parameter value, H word, L byte
Parameter value, H word, H byte
0x0E
[Get_Attribute_Single]
100
[PKW object] manufacturer-specific
1
[Instance number] always set to 1
1
[Attribute number] always set to 1
0x65
Parameter ID, L byte
0x60
Parameter ID, H byte
4
Parameter index, L byte
0
Parameter index, H byte
0x8E
[Get_Attribute_Single]
0x65
Parameter ID, L byte
0x40
Parameter ID, H byte
0x90
Parameter value, L word, L byte
0x01
Parameter value, L word, H byte
0x00
Parameter value, H word, L byte
0x00
Parameter value, H word, H byte
SIMOREG DC Master
05.05
SIEMENS AG
6RX1700-0AD76
Operating Instructions

Hide quick links:

Advertisement

Table of Contents
loading