11.32 Speed controller
(see also Section 8, Sheet G151)
further parameters for the speed controller P200 - P236
Speed controller adaptation
The parameters of the speed controller (Kp, Tn, droop) can be altered as a function of any connector to adapt the speed controller
optimally to a changing controlled system.
The diagrams below show the active P gain, the active Integration time and the active droop depending on the value of the set connector.
Adaptation of the P gain:
Adaptation of the integration time:
Adaptation of the droop:
For parameter pairs P225/P550, P226/P551 and P227/P552 all values can be set completely mutually independently, e.g., P550 does not
have to be greater than P225. The above diagrams show only the effect of the individual parameters.
Threshold 1 must always be set smaller than threshold 2, otherwise the fault message F058 is activated.
P550
P gain in the adaptation range
FDS
Value of Kp, if Influencing quantity ≤ Threshold 1
(G151)
P551
Integration time in the adaptation range
FDS
Value of Tn, if Influencing quantity ≤ Threshold 1
(G151)
P552
Droop in the adaptation range
FDS
Value of droop, if Influencing quantity ≤ Threshold 1
(G151)
P553
Source for the Influencing quantity of the Kp adaptation
*
Selection of which connector is connected at the influencing quantity for
FDS
adaptation of the n controllers P gain
0 = connector K0000
(G151)
1 = connector K0001
etc.
P554
Source for the Influencing quantity of the Tn-adaptation
*
FDS
Selection of which connector is connected at the influencing quantity for
adaptation of the n controllers integration time
(G151)
0 = connector K0000
1 = connector K0001
etc.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
KP
P550
P225
Threshold 1
Threshold 2
P556
P559
Tn
P551
P226
Threshold 1
Threshold 2
P557
P560
St
P552
P227
Threshold 1
Threshold 2
P558
P561
Value range
[Unit]
Steps
Input
selected in P553
Input
selected in P554
Input
selected in P555
0.10 to 200.00
0.01
0.010 to 10.000
[SW 1.7 and later]
[s]
0.001s
0.0 to 10.0
[SW 1.7 and later]
[%]
0.1%
All connector
numbers
1
All connector
numbers
[SW 1.7 and later]
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 4
P052 = 3
FS=3.00
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0.650
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0.0
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
11-59