Siemens 6RA7086-6KS22 Operating Instructions Manual page 505

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
P283
Filter time for actual value for EMF controller precontrol
FDS
Filtering of actual speed value at the input of the EMF controller precontrol.
(G165)
The purpose of this filter is to stabilize the EMF controller precontrol, even
when the actual speed signal is unsteady or distorted by harmonics.
P284
Set EMF controller P component to zero
*
0
Set controller P component to zero
FDS
(i.e. to obtain pure I controller)
(G165)
1
Controller P component is active
11.15 Ramp-function generator
(see also Section 8, Sheet G136 and Section 9)
See P639 and P640 for ramp-function generator setting parameters
P295
Mode for rounding the ramp-function generator
0
If the setpoint is reversed during ramp-up (or ramp-down),
FDS
acceleration (deceleration) is aborted and initial rounding of the
deceleration (acceleration) process begins immediately. The
(G136)
setpoint is not increased (decreased) any further, but the signal
at the ramp-function generator output has a breakpoint (i.e. a
step change in the acceleration rate).
1
If the setpoint is reversed during ramp-up or ramp-down,
acceleration/deceleration gradually changes to
deceleration/acceleration. The setpoint increases/decreases
further, but there is no breakpoint in the signal at the generator
output (i.e. there is no step change in the acceleration rate).
P296
Ramp-down time of ramp generator with emergency stop (OFF3)
FDS
When the "Emergency stop" command is issued, the drive must normally
(G136)
brake down to 0 speed along the current limit. If the mechanical design of
the drive makes this option impermissible or undesirable, then a value of > 0
can be set here. In this case, the drive brakes along the deceleration ramp
programmed here when the "Emergency stop" command is issued.
see also parameter P330
P297
Lower transition rounding of ramp generator with emergency stop
(OFF3)
FDS
see also parameter P330
(G136)
P298
Upper transition rounding of ramp generator with emergency stop
(OFF3)
FDS
see also parameter P330
(G136)
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
[SW 1.9 and later]
[SW 1.9 and later]
Ramp generator
output
Ramp generator
input
Ramp generator
output
Ramp generator
input
[SW 1.9 and later]
[SW 1.9 and later]
[SW 1.9 and later]
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0 to 10000
Ind: 4
[ms]
FS=0
1ms
Type: O2
0 to 1
Ind: 4
1
FS=1
Type: O2
0 to 1
Ind: 4
FS=0
1
Type: O2
0.00 to 650.00
Ind: 4
[s]
FS=0.00
0.01 s
Type: O2
0.00 to 100.00
Ind: 4
[s]
FS=0.00
0.01s
Type: O2
0.00 to 100.00
Ind: 4
[s]
FS=0.00
0.01s
Type: O2
Parameter list
See
Change
(Access /
Status)
P052 = 3
P051 = 40
on-line
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
on-line
P052 = 3
P051 = 40
on-line
P052 = 3
P051 = 40
on-line
P052 = 3
P051 = 40
on-line
11-41