Start-Up
Bits 12 to 15 contain the request identifier or the associated response identifier as shown in the
following list:
Request
identifier
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
If the drive has been unable to process the request, it does not return the associated response
identifier, but error identifier 7 (or 8) instead.
In this case, an error code defining the error in more detail as shown in the following list is returned
as a parameter value:
Error code
0
1
2
3
4
5
6
7
8
9
10
11
12
13
15
16
17
19
101
102
7-58
Request parameter value (word or double word)
Modify parameter value (word)
Modify parameter value (double word)
Request descriptive element
Request parameter value (array) (word or double word)
Modify parameter value (array - word)
Modify parameter value (array-double word)
Request number of array elements
Modify parameter value (array-double word) and store in EEPROM
Modify parameter value (array-word) and store in EEPROM
Modify parameter value (double word) and store in EEPROM
Modify parameter value (word) and store in EEPROM
Illegal parameter number (PNU)
Parameter value cannot be modified
Lower or upper value limit violated
Faulty subindex
Parameter is not indexed (no array)
Incorrect data type
Parameter value can only be reset
Descriptive element cannot be modified
PPO Write (acc. to "Information Report") is not available
Parameter description is not available
Incorrect access level
No parameterizing enable (P927)
Keyword missing
Text cannot be read cyclically
No text
PPO Write missing
Incorrect operating state
Value cannot be read cyclically
Parameter number currently deactivated
Channel not wide enough
Meaning
No request
Reserved
Reserved
Request text
Meaning
Response identifier
positive
0
1 or 2
1
2
3
-
4 or 5
4
5
6
-
5
4
2
1
15
No PNU specified
Visualization parameter
Key parameter P051 incorrectly set
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
negative
7 or 8
6RX1700-0AD76

Hide quick links: