Parameter list
PNU
Description
P778
Delay for output value at binary output 4
The logic level at the binary selectable output changes only if the internal
(G112)
signal level remains constant for the set delay period (internal signal level
changes which do not last as long as this delay period are not switched
through to the output)
11.41 Configuration of serial interfaces on basic converter
G-SST 1 (RS485 / RS232 on X300) (see also Section 8, Sheet G170 and Section 9)
P780
Selection of protocol for G-SST1 basic converter interface
*
0
Setting has no function
(G170)
2
USS protocol
8
for factory purposes
9
For internal factory test purposes
P781
Number of process data for G-SST1
*
When P780 = 0 or 9 is selected: Parameter is irrelevant
(G170)
When USS protocol (P780=2) is selected: Number of PZD elements
0
No process data are expected or sent in the USS protocol
1...16 Number of process data words in USS protocol (same number
applies to transmission and receipt)
The received PZD elements (1 to max. 16) are available at
connectors (K2001 to K2016) and, in some cases, bit-serially at
binectors for "internal wiring" purposes.
The PZD elements to be transmitted (1 to max. 16) are selected
in parameters P784.01 to P784.16.
P782
Length of parameter jobs for G-SST1
*
(G170)
This parameter is effective only when P780=2 (USS protocol).
0
No PKW data are expected or sent in the USS protocol.
3, 4
3 or 4 PKW data words are expected in the USS protocol and 3
or 4 PKW data words are also sent (for transmission of
parameter values).
127
Number of PKWs is determined by the telegram length
P783
Baud rate for G-SST1
*
1
300 baud
(G170)
2
600 baud
3
1200 baud
4
2400 baud
5
4800 baud
6
9600 baud
7
19200 baud
8
38400 baud
9
56700 baud
11
93750 baud
13
187500 baud
P784
Source for transmit data for G-SST1
*
Selection of connectors to be transferred as transmit data to the USS
(G170)
master via USS interface 1.
i001:
Selection for word 1
i002:
Selection for word 2
...
i016:
Selection for word 16
Applicable settings:
0 = connector K0000
1 = connector K0001
etc.
11-82
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
0, 2, 8, 9
Ind: None
1
FS=2
Type: O2
0 to 16
Ind: None
1
FS=2
Type: O2
0, 3, 4, 127
Ind: None
1
FS=127
Type: O2
1 to 13
Ind: None
1
FS=6
Type: O2
All connector
Ind: 16
numbers
FS=
1
i001: 32
i002: 167
i003: 0
i004: 33
i005-i016: 0
Type: L2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
05.05
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
6RX1700-0AD76

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents