Siemens 6RA7086-6KS22 Operating Instructions Manual page 547

6ra70 series, microprocessor-based converters from 6kw to 2500kw for variable-speed dc drives, simoreg dc master
Table of Contents

Advertisement

05.05
PNU
Description
P785
Options for G-SST1
i001:
0 = Bus terminator OFF
(G170)
1 = Bus terminator ON
i002:
0 = Bit 10 of the 1
by PLC".
1 = Bit 10 of the 1
PLC", i.e. when bit 10 = 0, all other bits of the 1
as well as receive words 2 to 16, are not written to connectors
K2001 to K2016, or to binectors B2100 to B2915. All these
connectors and binectors retain their old values.
P786
USS bus address for G-SST1
*
This parameter is functional only when P780=2 (USS protocol). Address via
(G170)
which the unit can be addressed in USS bus operation.
P787
Telegram failure time for G-SST1
The failure time set in this parameter is valid when setting P780=2 (USS
(G170)
protocol) is selected.
0.000
0.001...65.000 Time which may elapse between the receipt of two
Fault message F011 is activated if no valid telegram is received within this
time period.
Note:
The telegram monitoring function is active
from the receipt of the first error-free telegram after connection of the
electronics power supply
from the receipt of the first error-free telegram after the telegram monitor
has responded (i.e. monitoring timeout).
P788
Source for activation of F011
*
Selection of binector which will activate fault message F011 when it
(G170)
switches to log. "1"
2030 = binector B2030
2031 = binector B2031
r789
Diagnostic information for G-SST1
Free-running counter, overflow at 65535
(G170)
i001:
Number of error-free telegrams
i002:
Number of errored telegrams:
Byte frame, parity, overrun or BCC error
i003:
Number of byte frame errors
i004:
Number of overrun errors
i005:
Parity error
i006:
STX error:
Start interval before STX not observed,
telegram residual transfer time not observed,
delay time of LGE character too long,
erroneous STX, i.e. ≠ 02
i007:
Violation of telegram residual transfer time
i008:
Block check error
i009:
Incorrect telegram length:
With P782=3 or 4 only:
The length of the received telegram is ≠ P781 + P782
(Note: If the received values are correct, they will be processed
even when this error has been detected)
i010:
Timeout error:
No valid telegram has been received for a period exceeding the
setting in P787. After the occurrence of a timeout error, this
counter is not activated again until the next valid telegram is
received.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
st
receive word does not function as "Control
st
receive word does function as "Control by
No time monitoring
telegrams addressed to the unit before a fault message
is activated.
Value range
[Unit]
Steps
0 to 1
1
st
receive word,
0 to 30
1
0.000 to 65.000
[s]
0.001s
2030, 2031
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=0.000
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=2030
P051 = 40
Type: L2
Offline
Ind: 10
P052 = 3
Type: O2
11-83