Parameter list
PNU
Description
11.83 Configuration of SCB1 with SCI
U690
Configuration of analog inputs of SCI1
(2690)
Definition of type of input signals
Parameter value
(Z150)
(Z151)
0:
1:
2:
Notes:
- Only one signal can be processed per input. Voltage or current signals can
be evaluated.
- Voltage and current signals must be connected to different terminals.
- Only unipolar signals are permitted with settings 1 and 2, i.e. the internal
process quantities are also unipolar.
- When setting 2 is selected, an input current of< 2 mA causes shutdown on
faults (open-circuit monitoring)
- The offset compensation for the analog inputs is set in parameter U692.
i001: Slave 1, analog input 1
i002: Slave 1, analog input 2
i003: Slave 1, analog input 3
i004: Slave 2, analog input 1
i005: Slave 2, analog input 2
i006: Slave 2, analog input 3
U691
Smoothing time constant for analog inputs of SCI1
(2691)
Formula:
T = 2ms * 2 to the power of U691
i001: Slave 1, analog input 1
i002: Slave 1, analog input 2
(Z150)
i003: Slave 1, analog input 3
(Z151)
i004: Slave 2, analog input 1
i005: Slave 2, analog input 2
i006: Slave 2, analog input 3
U692
Offset compensation for analog inputs of SCI1
(2692)
Setting instructions, see Operating Instructions for SCI1
i001: Slave 1, analog input 1
i002: Slave 1, analog input 2
(Z150)
i003: Slave 1, analog input 3
(Z151)
i004: Slave 2, analog input 1
i005: Slave 2, analog input 2
i006: Slave 2, analog input 3
U693
Actual value output via analog outputs of SCI1
(2693)
Selection of connectors whose values are to be output (for details, see
Operating Instructions for SCI1)
i001: Slave 1, analog output 1
(Z155)
i002: Slave 1, analog output 2
(Z156)
i003: Slave 1, analog output 3
i004: Slave 2, analog output 1
i005: Slave 2, analog output 2
i006: Slave 2, analog output 3
U694
Gain for analog outputs of SCI1
(2694)
Setting instructions, see Operating Instructions for SCI1
i001: Slave 1, analog output 1
i002: Slave 1, analog output 2
(Z155)
i003: Slave 1, analog output 3
(Z156)
i004: Slave 2, analog output 1
i005: Slave 2, analog output 2
i006: Slave 2, analog output 3
11-156
Terminals
Terminals
X428/3, 6, 9
X428/5, 8, 11
-10 V ... + 10 V
- 20 mA ... + 20 mA
0 V ... + 10 V
0 mA ... + 20 mA
4 mA ... + 20 mA
Value range
[Unit]
Steps
[SW 1.9 and later]
0 to 2
1
[SW 1.9 and later]
0 to 15
1
-20.00 to 20.00
[SW 1.9 and later]
[V]
0.01V
All connector
[SW 1.9 and later]
numbers
1
-320.00 to 320.00
[SW 1.9 and later]
[V]
0.01V
SIMOREG DC Master
05.05
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind:6
P052 = 3
FS= 0
P051 =40
Type O2
on-line
Ind:6
P052 = 3
FS= 2
P051 =40
Type O2
on-line
Ind:6
P052 = 3
FS= 0
P051 =40
Type I2
on-line
Ind:6
P052 = 3
FS= 0
P051 =40
Type L2
on-line
Ind:6
P052 = 3
FS= 10.00
P051 =40
Type I2
on-line