Therefore, the Disabled schedule has highest priority, and the Card Only schedule
has lowest priority.
Note: Readers must be enabled in two places, in Panel Configuration and here. Go Panel
Configuration > Settings > Behaviour Settings tab. See
Note: The access mode defined here for the door can be overridden by a card assigned with
a VIP card type. (See
VIP card type.)

Configuring Door Inputs

The Inputs tab allows you to configure the following settings:
Four inputs are associated with each of the doors on a MPA2C3 panel:
The Inputs tab allows you to configure the following settings for each door:
Note: For 2-Door and 4-Door, the input configuration is same.
60
PIN only
Card only
Configuring People on page 69
Input Name
Input Modes
Shunt and Debounce
Scheduling
Status – Provides door status information (Doorcnt).
Egress – Allows the door to open or close normally without generating an alarm (REX).
Tamper A – Reports abnormal handling of the reader device or wiring for Reader A.
Tamper B – Reports abnormal handling of the reader device or wiring for Reader B.
Define the Status, Egress, and Tamper input modes.
Specify the Status, Egress, and Tamper shunt time, or the period of time the
door's normal state will be ignored.
Specify the Status, Egress, and Tamper debounce time, or the period of time the
input
must remain in its new state before it is recognized as being in the new state.
Specify the schedules for the Status, Egress, and Tamper inputs.
• Enable or disable Auto-Relock for the Status inputs.
Figure 2-10
on
for information about assigning a
MPA2C3 User Manual
page
31.