3. Select Input Modes.
Table 2-6
Configura-
tion
Normally
State
Resistor
Value
Auto-Relock
Output
62
Description
Normally Closed means that the input's normal
state is closed. (Default setting).
Normally Open means that the input's normal state
is open.
Unsupervised means that the input's electrical cir-
cuit is wired in one path without alternative paths
supervised by resistors. (Default setting)
Supervised means that the input's electrical circuit
is wired in one path with alternative paths super-
vised by resistors. If you select Supervised, then you
must select a Resistor value.
Specifies the resistor values being used in the
supervised modes. Select from: 1K ohms, 2.2K
ohms, 4.7K ohms, or 10K ohms. The default is 2.2K
Ohm.
Note: when using MPA2S5 Door
connection cable, the State for
Door contact (DrCnt) must be set to
Supervised with 2.2K ohms. The
State for Request to Exit button
must be set to Unsupervised
Causes the door to re-lock immediately when the
door status switch closes after entry. The output
relay that controls the door strike de-energizes
when the associated input returns to normal state
instead of remaining energized for the duration of
the pulse time. To enable Auto-Relock, de-select the
Disable check box, and select the associated output
from the drop-down list.
Select an Output value for Auto-Relock.