5. Connect the fire output wiring to the FACP input.
See the installation manual for the correct wiring of the FACP input.
FACP settings for Interlocks and Reporting only
The section GENERAL, SHUNT AND DEBOUNCE and SCHEDULING have no effect
on the triggered FACP input unlocking all doors at all. E.G a shunted or debounced
value in this section will not shunt or delay all the door outputs to fail-safe state
(de-energized)
The GENERAL, SHUNT AND DEBOUNCE and SCHEDULING sections allows you to
configure the following settings:
•
•
•
Define the FACP input reporting features.
•
•
•
1. In Panel configuration/advanced/FACP Input, Go to section General – For
MPA2C3 User Manual
Input Name
Shunt and Debounce
Scheduling
Specify the FACP input shunt time, or the period of time the state of the FACP
input will be ignored (only for reporting - interlocking).
Specify the FACP input debounce time, or the period of time the FACP input
must remain in its new state before it is recognized as being in the new state
(only for reporting).
Specify the FACP input schedules.
Interlocks and Report only.
115