Product Description
SECTION 1
1.1 Inventory
1.2 Features and Options
12
Product Description
The Fire•Lite MS-9600 is a compact, cost effective, intelligent addressable FACP (Fire
Alarm Control Panel) with an extensive list of powerful features. The combination of
Fire•Lite's newer series devices and legacy 300 Series devices, along with the MS-9600
FACP, offer the latest in fire protection technology. The power supply and all
electronics are contained on a single circuit board housed in a metal cabinet, providing
a complete fire control system for most applications. Optional modules, which plug
into the main circuit board, are available for special functions. Available accessories
include LED, graphic and LCD annunciators, reverse polarity/city box transmitter,
digital alarm communicator/transmitter, SLC expansion module, local and remote
upload/download software and remote power expansion. The MS-9600E offers the
same features as the MS-9600 but allows connection to 220/240 VAC input.
Note: Unless otherwise specified, the term MS-9600 is used in this manual to refer to
both the MS-9600 and the MS-9600E FACPs.
When the MS-9600 shipment is received, check to make certain that all parts have been
included in the shipment. The MS-9600 shipment should consist of one of each of the
following:
main circuit board with display
backbox with door
plastic bag containing screws, cables, key, etc.
manual
•
Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7
requirements
•
Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and
7 requirements
•
318 addressable device capacity for each SLC loop (159 detectors and 159
control/monitor modules)
•
99 software zones
•
Up to four onboard NACs (Notification Appliance Circuits):
four Style Y (Class B) or two Style Z (Class A)
•
Additional NAC capability using control modules
•
7.0 amps total power for NACs and 24 VDC auxiliary power outputs in alarm
•
Two programmable relay outputs and one fixed trouble relay
•
EIA-232 Printer/PC interface (variable baud rate)
•
80-character LCD display (backlit)
•
Real-time clock/calendar with daylight savings time control
•
History file with 1,000 event capacity
•
Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
•
Waterflow selection per module point
•
Alarm verification selection per detector point
•
Walktest, silent or audible
Inventory
MS-9600 PN 51335:E1 2/14/08