Ann-Bus Devices; Guidelines - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

ANN-BUS Devices

3.
Secure the ANN-SEC to the circuit board with the supplied screw.
FACP Circuit Board
2.7 ANN-BUS Devices
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.

Guidelines

A variety of optional annunciation devices can be connected to an ANN-BUS communication
circuit. ANN Series devices can be connected to the primary communication circuit (EIA-485)
terminals on TB3. A secondary communication circuit (EIA-485) for these devices is available
at TB1 on the ANN-SEC card.
When using one ANN-BUS circuit, up to eight (8) annunciators can be supported.
When using both ANN-BUS communication circuits, the primary circuit supports up to three
(3) annunciators and the secondary circuit supports up to (5) annunciators.
Compatible devices include:
– ANN-80 LCD Annunciator
– ANN-80C LCD Indicator (Canadian Applications)
– ANN-S/PG Serial/Parallel Printer Interface Module
– ANN-I/O LED Driver Module
– ANN-LED Annunciator Module
– ANN-RLY Relay Module (can be mounted in the FACP chassis)
When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in
the system.
The panel is capable of operating a primary ANN-BUS (TB3) and a secondary ANN-BUS
(TB1 on ANN-SEC card) simultaneously.
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
connector to J13 on
main circuit board
Figure 2.17 Installing the ANN-SEC Option Card
J1
ANN-SEC
TB1
standoff and screw
Installation
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrp-2002eMrp-2002c