Refer to the following table and set the parameters: (0 to 99: positive logic, 100 to 199: negative logic)
Setting
Signal
Positive
Negative
Name
logic
logic
0
100
RUN
Inverter running
1
101
SU
Up to frequency
Instantaneous power
2
102
IPF
failure/undervoltage
3
103
OL
Overload alarm
Output frequency
4
104
FU
detection
Second output frequency
5
105
FU2
detection
Third output frequency
6
106
FU3
detection
Regenerative brake
7
107
RBP
prealarm
Electronic thermal relay
8
108
THP
function prealarm
10
110
PU
PU operation mode
11
111
RY
Inverter operation ready
12
112
Y12
Output current detection
13
113
Y13
Zero current detection
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
PID forward/reverse
16
116
RL
rotation output
17
MC1
Electronic bypass MC1
18
MC2
Electronic bypass MC2
19
MC3
Electronic bypass MC3
20
120
BOF
Brake opening request
25
125
FAN
Fan alarm output
Heatsink overheat
26
126
FIN
pre-alarm
27
127
ORA
Orientation completion
28
128
ORM
Orientation fault
30
130
Y30
Forward rotation output
31
131
Y31
Reverse rotation output
Regenerative status
32
132
Y32
output
33
133
RY2
Operation ready 2
34
134
LS
Low speed output
35
135
TU
Torque detection
36
136
Y36
In-position
Start-time tuning
39
139
Y39
completion signal
Functions
Output during operation when the inverter output
frequency rises to or above [Pr. 13 Starting frequency].
Output when the output frequency reaches to the set
*1
frequency.
Output at occurrence of an instantaneous power failure
or undervoltage protection activation.
Output while stall prevention function is activated.
Output when the output frequency reaches the
frequency set in [Pr. 42] (for reverse rotation [Pr. 43]).
Output when the output frequency reaches the
frequency set in [Pr. 50].
Output when the output frequency reaches the
frequency set in [Pr. 116].
Output when 85% of the regenerative brake duty set in
[Pr. 70] is reached.
For
F700
Output when the electronic thermal value reaches 85%
of the trip level. (Electronic thermal relay function
protection (E.THT/E.THM) activates, when the value
reached 100%.)
Output when the PU operation mode is selected.
Output when reset process is completed (when the
inverter can be started by switching the start signal ON
or while it is running) after powering ON the inverter.
Output when the output current is higher than the [Pr.
150] setting for longer than the time set in [Pr. 151].
Output when the output current is higher than the [Pr.
152] setting for longer than the time set in [Pr. 153].
Output when the feedback value falls below the lower
limit of PID control.
Output when the feedback value rises above the upper
limit of PID control
Output when forward rotation is performed in PID
control.
Used when the bypass-inverter switchover function is
used.
Output to open the brake when the brake sequence
function is selected.
Output at the time of a fan alarm.
Output when the heatsink temperature reaches about
85% of the heatsink overheat protection providing
temperature.
When orientation is valid
Output when the motor is running in forward direction.
Output when the motor is running in reverse direction.
Output in the regeneration status under vector control
operation.
*4
Output during vector control or pre-excitation operation
under Real sensorless vector control or vector control.
Output when the output frequency reduces below the
[Pr. 865] setting.
Output when the motor torque rises above the [Pr. 864]
setting.
Output when the number of droop pulses has fallen
below the setting value.
Output on completion of start-time tuning.
Operation
, setting can be made for the 75K or more.
*4
62
SPECIFICATIONS