(2) Inverter power ON/OFF timing chart
Output
[Pr.13 Start
frequency
frequency]
ON
Power supply
R/L1, S/L2, T/L3
Start
STF (STR)
Inverter output shutoff
Approx.1s
(Initial reset time)
*1
The inverter output is shut off immediately (between more than 15ms and less than 100ms) after the power is switched OFF.
If more than 100ms has elapsed after the power is switched OFF, the inverter protective circuit is automatically reset by
powering ON again.
*2
Inverter output immediately shuts off if bus voltage of inverter drops to the specified value or lower for more than 10ms after
power OFF.
(3) Inverter instantaneous power failure timing chart
Output
frequency
Power supply
R/L1, S/L2, T/L3
Start STF (STR)
Inverter output shutoff
Instantaneous
power failure IPF
Fault output relay
*1
For
instantaneous power failure
,
A700
F700
automatic restart after instantaneous power failure is activated and fault output signal is not switched ON when 0 or any of 0.1 to
5s is set in [Pr. 57] for the 55K or less and 0 or any of 0.1 to 30s is set for the 75K or more.
When power is restored after inverter output shutoff in
starting frequency. However, automatic restart after instantaneous power failure becomes active when the automatic restart
after instantaneous power failure function [Pr.57] is set to "0" or "0.1 to 5s".
*2
An instantaneous power failure of longer than 100ms is identical to a long-time power failure. (Refer to (2) inverter power ON/
OFF timing chart.) If the start signal is ON, the inverter is restarted when the power is restored.
common
ON
Approx. 20ms
[Pr.13 Start
frequency]
A700
Within 15ms
E700
Approx. 20ms
Within 10ms
ON
ON
*1
*1
activates when the power is restored within 15 to 100ms. Note that
IPF
Approx. 20ms
Approx. 20ms
common
Coasting
F700
A700
F700
D700
More than 15ms
15ms to 100ms or less
ON
ON
ON
, the inverter does not output fault and re-starts from the
E700 D700
35
SPECIFICATIONS
The motor is coasted to a
stop
t
A700
F700
15ms to 100ms or less *1
E700
D700
More than 10ms *2
ON
t
E700
D700
1
More than 10ms*
1