Terminal
Terminal
Symbol
Name
Interface : conforms to USB1.1
Transmission speed : 12Mbps
Connector :
A700
USB
USB B connector
connector
(B receptacle)
E700
USB mini B connector
(mini B receptacle)
Inverter
output
S1
shutoff
(Line 1)
Inverter
output
S2
shutoff
(Line 2)
Safety
monitor
output
SO
(open
collector
output)
Output
shutoff
SC
terminal
common
*1
Terminal function can be changed using [Pr. 178 to Pr. 189 Input terminal assignment].
*2
Terminal function can be changed using [Pr. 190 to Pr. 196 Output terminal assignment].
*3
The description at a fault occurrence can be output by 4 bit digital signal using [Pr. 76 Fault code output selection].
*4
Low indicates that the open collector output transistor is ON (conducts).
High indicates that the transistor is OFF (does not conduct).
*5
Monitor to be output to terminal FM can be changed using [Pr. 54 FM terminal function selection].
*6
Monitor to be output to terminal AM can be changed using [Pr. 158 AM terminal function selection].
Rating, etc.
Application Explanation
FR Configurator can be operated by
connecting the inverter to the
personal computer through USB.
Inverter output is shutoff depending
on shorting/opening between S1 and
SC, or between S2 and SC. At initial
state, terminal S1 and S2 are shorted
to terminal SC with a shorting wire.
When using the safety stop function,
remove this shorting wire, and
connect to a safety relay module.
Switched low when inverter output is
shutoff by safety stop function, and
high during other state.
Common terminal for terminals S1,
S2 and SO. Connected to terminal
SD inside of the inverter.