parameters not registered in the user group can not
be read.)
To register a parameter to the user group, set its
parameter number in [Pr. 173]. To delete a parameter
in the user group, set its parameter number in [Pr.
174] . Set [Pr. 172 = 9999] to batch delete parameters
registered.
2.18.5 Password function [Pr. 296, 297]
Registering 4-digit password can restrict parameter reading/writing.
[Pr. ]
Name
296
Password lock level
297
Password lock/unlock
(1) Parameter reading/writing restriction level
[Pr. 296]
Level of reading/writing restriction by PU/NET mode
operation command can be selected by [Pr. 296].
PU Mode Operation
[
Pr. 296
]
Command
Setting
Read
Write
∗1
9999
1, 101
2, 102
3, 103
×
4, 104
5, 105
×
6, 106
*1
If the parameter reading is restricted by the [Pr. 160]
setting, those parameters are unavailable for reading
even when " " is indicated.
*2
If the parameter writing is restricted by the [Pr. 77] setting,
those parameters are unavailable for writing even when
" " is indicated.
*3
Parameter access from unit where parameter is written in
PU operation mode (initially set to operation panel,
parameter unit) is restricted. (Refer to page 436 for PU
mode operation command source selection)
*4
Parameter access in NET operation mode with RS-485
communication is restricted.
Initial Value
9999
9999
NET Mode
Operation
∗3
Command
∗4
Read
Write
∗2
∗1
∗2
×
×
×
×
×
×
×
×
×
×
: enabled, ×: disabled
[Pr. 77, Pr. 160 and Pr. 991] can always be read,
independently of the user group setting.
[Pr. 77, Pr. 160, Pr. 172 to Pr. 174] cannot be registered
to the user group.
When [Pr. 173, Pr. 174] is read, 9999 is always
displayed.
When any value other than 9999 is set in [Pr. 172], no
function is available.
D700
Setting Range
Select restriction level of parameter reading/
1 to 6, 101 to 106
writing when a password is registered.
9999
No password lock
1000 to 9998
Register a 4-digit password
Displays password unlock error count. (Reading
(0 to 5)
only)
(Valid when Pr. 296 = "101" to "106")
(9999)
No password lock (Reading only)
(2) Password lock/unlock [Pr.296, Pr.297]
1) Lock
Set parameter reading/writing restriction level by
Pr. 296. ([Pr. 296 ≠ 9999])
When the setting is "101 to 106", the number of
password unlock errors (0 to 5 times) is displayed
when [Pr. 297] is read.
(When the [Pr. 296] setting is "1 to 6", the number
is not displayed.
Write four-digit number (1000 to 9998) in [Pr.297]
as a password.
(When [Pr. 296 ="9999"], Pr.297 cannot be written.)
Once password is registered, parameter reading/
writing is restricted with the restriction level set in
[Pr. 296] until password unlock.
After registering a password, a read value of [Pr.
297] is always "0" to "5". When a password
restricted parameter is read/written,
displayed. Even if a password is registered,
parameters which the inverter itself writes, such
as inverter parts life, are overwritten occasionally.
Even if a password is registered, [Pr. 991 PU
contrast adjustment] can be read/written when a
parameter unit (FR-PU04/FR-PU07) is connected.
387
PARAMETER
Description
is
2