Mitsubishi Electric FR-A700 Technical Manual page 220

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

2) FR-F700 series
Select the inverter control method from V/F
control and Simple magnetic flux vector control.
[Pr. ]
Name
80
Motor capacity
3) FR-E700 series
Select the inverter control method from V/F
control, Advanced magnetic flux vector control,
General-purpose magnetic flux vector control.
[Pr. ]
Name
80
Motor capacity
81
Number of motor poles
450 Second applied motor
Control method
800
selection
* When [Pr.80 Motor capacity = 9999] or [Pr.81 Number of motor poles = 9999], control method is V/F control regardless of [Pr.800] setting.
[Pr. 80, 81]
[Pr. 800] Setting
Other than 9999
([Pr. 800] initial value)
9999
* Control method is V/F control regardless of the setting value of [Pr. 800] when [Pr. 80 Motor capacity = 9999] or [Pr. 81 Number of motor
poles = 9999].
4) FR-D700 series
Select the inverter control method from V/F
control and General-purpose magnetic flux vector
control.
[Pr. ]
Name
80
Motor capacity
450 Second applied motor
Initial
Setting Range
Value
55K or less
0.4 to 55kW
9999
75K or more
0 to 3600kW
9999
Initial
Setting Range
Value
0.1 to 15kW
9999
9999
2, 4, 6, 8, 10
9999
9999
0, 1
9999
9999
20
20
30
Control Method
20
Advanced magnetic flux vector control
30
General-purpose magnetic flux vector control
*
V/F control
Initial
Setting Range
Value
0.1 to 7.5kW
9999
9999
0, 1
9999
9999
Simple magnetic flux vector control
Set the applied motor capacity.
V/F control
You can set the thermal characteristic of the
electronic thermal for the second motor by setting
[Pr. 450
9999]. At this time, control method does
not change.(Depends on the settings of [Pr. 80, 81,
800])
Set the applied motor capacity.
V/F control
Set the number of motor poles.
V/F control
Set when using the second motor.
Function invalid ([Pr. 71] is valid.)
Advanced magnetic flux vector control
V/F control *
General-purpose magnetic flux vector
control
You can set the thermal characteristic for the
second motor by setting [Pr. 450
time, control method does not change. (Depends
on the settings of [Pr. 80])
General-purpose magnetic flux vector control
Set the applied motor capacity.
V/F control
Set when using the second motor.
Function invalid ([Pr. 71] is valid.)
254
PARAMETER
Description
Description
9999]. At this
Description