2.1.2
FR-F700
In the initial setting, only the simple mode parameters are displayed. Set [Pr. 160 User group read selection] as required.
indicates simple mode parameters.
• The parameters marked with
in the table allow its setting to be changed during operation even if 0 (initial value) is
set in [Pr. 77 Parameter write selection] .
Initial
[Pr. ]
Name
Value
160
User group read selection
9999
[Pr.]
Name
Torque boost
0 to 30%
0
1
Maximum frequency
0 to 120Hz
Minimum frequency
0 to 120Hz
2
Base frequency
0 to 400Hz
3
4
Multi-speed setting (high speed)
0 to 400Hz
Multi-speed setting (middle speed)
0 to 400Hz
5
Multi-speed setting (low speed)
0 to 400Hz
6
Acceleration time
0 to 3600/360s
7
Deceleration time
0 to 3600/360s
8
9
Electronic thermal O/L relay
0 to 500/0 to 3600A
10
DC injection brake operation frequency
0 to 120Hz, 9999
11
DC injection brake operation time
0 to 10s
12
DC injection brake operation voltage
0 to 30%
13
Starting frequency
0 to 60Hz
14
Load pattern selection
0, 1
15
Jog frequency
0 to 400Hz
16
Jog acceleration/deceleration time
0 to 3600/360s
17
MRS input selection
0, 2
18
High speed maximum frequency
120 to 400Hz
19
Base frequency voltage
0 to 1000V, 8888, 9999
Acceleration/deceleration reference
20
1 to 400Hz
frequency
21
Acceleration/deceleration time increments 0, 1
22
Stall prevention operation level
0 to 150%, 9999
Stall prevention operation level
23
0 to 200%, 9999
compensation factor at double speed
24
Multi-speed setting (speed 4)
0 to 400Hz, 9999
25
Multi-speed setting (speed 5)
0 to 400Hz, 9999
26
Multi-speed setting (speed 6)
0 to 400Hz, 9999
27
Multi-speed setting (speed 7)
0 to 400Hz, 9999
PARAMETER
Setting
Remarks
Range
9999
Only the simple mode parameters can be displayed.
0
Simple mode+extended mode parameters can be displayed.
Only the parameters registered to the user group can be
1
displayed.
Minimum Setting
Setting Range
Initial value Reference
Increments
6/4/3/2/
0.1%
1.5/1%
*1
0.01Hz
120/60Hz
*2
0.01Hz
0Hz
0.01Hz
60Hz
0.01Hz
60Hz
0.01Hz
30Hz
0.01Hz
10Hz
0.1/0.01s
5/15s
*3
0.1/0.01s
10/30s
*3
Rated inverter
0.01/0.1A
*2
*2
current
0.01Hz
3Hz
0.1s
0.5s
0.1%
4/2/1%
*4
0.01Hz
0.5Hz
1
1
0.01Hz
5Hz
0.1/0.01s
0.5s
215, 234
1
0
0.01Hz
120/60Hz
*2
0.1V
9999
0.01Hz
60Hz
1
0
0.1%
120%
0.1%
9999
0.01Hz
9999
0.01Hz
9999
0.01Hz
9999
0.01Hz
9999
152
• Symbols in the option column indicate parameters which function when an option is mounted.
......... FR-A7AX,
......... FR-A7NC,
......... FR-A7NP
• These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485
communication.
• Symbols in the control mode-based correspondence table indicate the following;
: Usable parameter
×: Unusable parameter
• Symbols in the parameter copy, parameter clear, and all parameter clear columns indicate the following;
: Valid
×: Invalid
[Pr.]
Option
244
0
232
1
232
2
244
3
216
4
216
5
216
6
234
7
234
8
379
9
328
10
328
11
328
12
232
13
244
14
215
15
16
56
17
232
18
244
19
234
20
234
21
335
22
335
23
216
24
216
25
216
26
216
27
.......... FR-A7AY,
.......... FR-A7AR,
......... FR-A7ND,
......... FR-A7NL,
Control Mode-based
Instruction Code
Correspondence Table
Simple
V/F
magnetic
Read
Write Extended
control
flux vector
control
×
00
80
0
01
81
0
02
82
0
03
83
0
04
84
0
05
85
0
06
86
0
07
87
0
08
88
0
09
89
0
0A
8A
0
0B
8B
0
0C
8C
0
0D
8D
0
0E
8E
0
0F
8F
0
10
90
0
11
91
0
12
92
0
13
93
0
14
94
0
15
95
0
16
96
0
17
97
0
18
98
0
19
99
0
1A
9A
0
1B
9B
0
152