2.4.2
When Jog operation [Pr. 15, 16]
You can set the frequency and acceleration/deceleration
time for Jog operation. Jog operation can be performed
from either of the External or the PU operation mode.
This operation can be used for conveyor positioning, test
operation, etc.
[Pr. ]
Name
15
Jog frequency
Jog
acceleration/
16
deceleration
time
* When the setting of [Pr. 21 Acceleration/deceleration time increments] is "0" (initial value), the setting range is "0 to 3600s" and the
setting increments are "0.1s", and when the setting is "1", the setting range is "0 to 360s" and the setting increments are "0.01s".
Pr. 21
[
] is not available for
(1) Jog operation from outside
When the JOG signal is ON, a start and stop can
be made by the start signal (STF, STR). (The JOG
signal is assigned to the terminal JOG in the initial
setting.)
Three-phase AC
power supply
Forward rotation start
Reverse rotation start
JOG signal
Connection diagram for external Jog operation
(2) Jog operation from PU
Press
to choose the Jog operation mode.
Hold down the
operation.
When [Pr. 79 Operation mode selection = "4"],
pressing
/
the inverter and pressing
(common)
Initial
Setting
Value
Range
5Hz
0 to 400Hz Set the frequency for Jog operation.
Set the acceleration/deceleration time for Jog operation. As the acceleration/
deceleration time, set the time taken to reach the frequency (initial value is 60Hz) set in
[Pr. 20 Acceleration/deceleration reference frequency].
0 to 3600/
0.5s
Acceleration/deceleration time can not be set separately.
360s
*
When [Pr. 29 Acceleration/deceleration pattern selection = "1"], the acceleration/
deceleration time of S-pattern acceleration/deceleration A is the time required to reach
[Pr. 3 Rated motor frequency].
. Setting range of [Pr. 16] is 0 to 3600s, and the increment is 0.1s.
D700
Inverter
R/L
U
1
S/L
V
Motor
2
T/L
W
3
STF
STR
JOG
SD
10
2
5
(or
) key to perform
of the parameter unit starts
stops the inverter.
common
During Jog operation, the second acceleration/deceleration
via RT signal cannot be selected.
functions are valid)
This function is invalid when [Pr. 79 = "3"].
Jog operation is invalid under position control. For
Jog operation is invalid with the position control of vector
control.
Description
Output
frequency(Hz)
[Pr.20]
[Pr.15
Forward
rotation
Jog frequency]
setting range
[
Pr.16
JOG signal
Forward
rotation STF
ON
Reverse
rotation STR
R/L
Three-phase AC
S/L
power supply
T/L
215
PARAMETER
(The other second
Time
Reverse
rotation
]
ON
ON
Inverter
U
1
Motor
V
2
W
3
FR-DU07
,
A700
2