(3) Bias/gain adjustment [Pr. 300 to 303, 329]
For setting output frequency of when input signal is 0,
use [Pr. 300] for BCD code input, and use [Pr. 302] for
binary input.
For setting output frequency of maximum input signal
(999 or 9999 for BCD code input, and FFF
for binary input), use [Pr. 301] for BCD code input,
and use [Pr. 303] for binary input.
[Pr. 301]
[Pr. 303]
[Pr. 300]
Bias
[Pr. 302]
(Hz)
0
0
Digital input signal
When "9999" is set in [Pr. 301] or [Pr. 303], the digital
input value is set as the output frequency (when [Pr.
329 = 1]). When this setting method is used, "bias"
setting ([Pr. 300] or [Pr. 302]) cannot be made.
or FFFF
H
H
Gain
999(9999) BCD
[Pr. 304 =0 2]
FFF
(FFFF
) Binary [Pr. 304 =1 3]
H
H
231
When 9999 is set in [Pr. 301] or [Pr. 303], use [Pr. 329]
for changing the setting increments.
Set
Digital input
=
Frequency
signal value
[Example] When [Pr. 304 = 0], [Pr. 301 = 9999], [Pr. 329
= 1] and BCD code = 120 is input
120
0
120
(Hz)
With the setting above, changing [Pr. 329] setting will
change the output frequency as follows.
[Pr. 329] Setting
BCD Code
0
1
2
3
PARAMETER
[Pr. 329] input increments
Digital input signal
(BCD)
Set
Frequency
1200H
Z
120H
Z
120
12.0H
Z
1.20H
Z
2