Mitsubishi Electric FR-A700 Technical Manual page 379

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

(3) Connection diagram
Sink logic
Pr. 128 = 41
Pr. 183 = 14
MCCB
Pr. 190 = 15
Power
supply
Pr. 191 = 14
*5
Pr. 192 = 16
Forward rotation
Reverse rotation
PID control selection
Main speed command
setting potentiometer
*1
Feedback value of
dancer roll position
(4) I/O signals and parameter setting
Set "40 to 43" in [Pr. 128 ] to perform dancer control.
(Disable PID output interruption function ([ Pr. 575 =
9999]) during dancer control.)
Set "14" in any of [Pr. 178 to Pr. 184 (input terminal
function selection)] to assign PID control selection
signal (X14) to turn the X14 signal ON.
When the X14 signal is not assigned, only the Pr. 128
setting makes dancer control valid.
Input the main speed command (External, PU,
Network). The main speed command in any
operation mode can be input. (Note that terminal 4
can not be used as the main speed command.)
(Terminal 2 is not available for speed control when
Signal
Terminal Used
Depending on
X14
[Pr. 178 to Pr. 184]
4
4
FUP
FDN
Depending on
[Pr. 190 to Pr. 192]
RL
PID
SE
SE
*1
When the X14 signal is not assigned, only the [Pr. 128 = 40 to 43] setting makes dancer control valid.
*2
The shaded area indicates the parameter initial value.
*3
When 100 or larger value is set in any of Pr. 190 to Pr. 192 (output terminal function selection), the terminal output has negative logic.
(For details, Refer to page 61)
Inverter
Motor
R/L1
U
V
IM
S/L2
T/L3
W
STF
STR
MRS(X14)
*3
SD
Upper limit
(FUP)RUN
*2
(FDN)FU
Lower limit
*2 *5
10
2
5
Output signal common
SE
4
*4
Function
PID control
Turn ON X14 signal to perform dancer
control.
selection
*1
Input the signal from the dancer roller
detector (measured value signal).
Measured value
4 to 20mA... 0 to 100%
input
0 to 5V........ 0 to 100%
0 to 10V...... 0 to 100%
Output to indicate that the measured
Upper limit
value signal exceeded the maximum
output
value [Pr. 131].
Lower limit
Output when the measured value signal
falls below the minimum value [Pr. 132].
output
Output is "ON" when the output
Forward
indication of the parameter unit is
(reverse) rotation
forward rotation (FWD) and "OFF" when
direction output
reverse rotation (REV) or stop (STOP).
During PID
Turns ON during PID control.
control activated
Output terminal
Common terminal for open collector
output terminal.
common
*1
The main speed command differs according to each
operation mode (external, PU, communication)
*2
The used output signal terminal changes depending on
the Pr. 190 to Pr. 192 (output terminal selection) setting.
has only one open collector output terminal.
D700
*3
The used input signal terminal changes depending on the
Pr. 178 to Pr. 184(input terminal selection) setting.
*4
The AU signal need not be input.
*5
Available only in
E700
[Pr. 561 PTC thermistor protection level
. Terminal 2 functions as a PTC thermistor
D700
input terminal.)
Input the set point using [Pr. 133], then input the
measured value signal (dancer roller position
detection signal) across terminal 4 and 5 of the
inverter.
When [Pr. 128 ] = "0" or X14 signal is OFF, normal
inverter operation is performed without dancer
control.
Turning ON/OFF of bit of the terminal, to which X14
signal is assigned through network as RS-485
communication, enables dancer control.
Description
Set 14 in any of [Pr. 178 to Pr. 184].
[Pr.128 = 40, 41, 42, 43]
[Pr.267 = 0]
[Pr.267 = 1]
[Pr.267 = 2]
[Pr.128 = 40, 41, 42, 43]
[Pr.131 = 9999]
Set 15 or 115 in any of [Pr. 190 to Pr. 192].
[Pr.128 = 40, 41, 42, 43]
[Pr.132 ≠ 9999]
Set 14 or 114 in any of [Pr. 190 to Pr. 192].
Set 16 or 116 in any of [Pr. 190 to Pr. 192].
Set 47 or 147 in any of [Pr. 190 to Pr. 192].
413
PARAMETER
.
9999] in
Parameter Setting
*2
2
*3
*3
*3
*3