2) Read [C29 (Pr. 925)] and set the compensation
value.
Compensation using the operation panel
(a)
(FR-DU07)
Select C29 in parameter setting mode.
Current compensation command value
is displayed. *1
*1
Take caution not to turn
"102.7" and "C29" are
alternately displayed,
then "102.7" is set as
compensation value.
at this point.
53
(b) Calibration using the parameter unit (FR-
PU07)
SETTING MODE
Pr.No.
Read Pr. 925 in parameter setting mode.
925
<READ>
925
0
Set<WRITE>
Ext<READ>
925
Current compensation
0
setting
101.0%
Current compensation
Ext
102.7%
command value
925
0
101.0%
Ext
102.7%
925
0
"102.7" is set as compensation
102.7%
value.
Completed
Adjusting a compensation value as desired
925
0
Input "99.2" using a numerical key
99.2%
Ext
102.7%
925
0.00
"99.2" is set as compensation value.
99.2%
Completed
3) After
compensation,
calibration status switch (SW2) to the original
position.
Always return the SW2 to the original position
after calibration. Starting the motor in the
calibration status results in motor thermal (E.
THM), shutting off the inverter output.
SW2
SPECIFICATIONS
reset
the
thermistor
1